SCOPE: This specification covers a non-contacting, ultrasonic
Level Indicating Transmitter as manufactured by Greyline
Instruments Inc., Massena, New York / Long Sault, Ontario. The
instrument shall provide for indicating, transmitting and control
of the material level in a vessel, or proximity of a target to
the Instrument Sensor.
A. PERFORMANCE SPECIFICATIONS
To consist of a non-contacting ultrasonic sensor,
connecting cable, and a remote enclosure with indicating,
transmitting and controlling electronics.
Measurement accuracy shall be ±0.25% of Range or 2 mm
(0.08"), whichever is greater, and shall be
automatically temperature compensated.
Sensor cable shall be RG62AU coaxial with total length as
required for installation, not to exceed 500' (152 m).
System shall have no moving parts and shall not contact
the material being measured.
B. NON-CONTACTING SENSOR
Sensor shall be constructed of PVC and Teflon.
The sensor shall have a minimum deadband or blanking of
12" (305mm) and a maximum range of 32 ft. (10 m),
and have an operating frequency of 42 kHz with an
ultrasonic beam angle of 8ø.
Sensor shall withstand accidental submersion to 20 psi.
Sensor operating temperature shall be from -40°F to
150°F (-40°C to 65°C).
Sensor shall include integral temperature sensor.
Temperature sensors requiring separate mounting and wire
runs shall not be accepted.
C. SENSOR CONNECTING CABLE
Provide RG62AU coaxial cable 25' (7.6 m) continuous length,
with waterproof, potted bond to the Sensor head.
Extended sensor cable shall be RG62AU coaxial to a
maximum of 500' (152 m). Cable shall be spliced with screw
terminal connections in manufacturer's recommended steel
NEMA4 Junction Box.
Level and temperature signals shall be conducted on one
single coaxial cable. Separate or multiple-conductor
cables shall not be accepted.
Sensor cable shall be installed in grounded metal
conduit.
D. INDICATING TRANSMITTER
The Indicating Transmitter shall be housed in a
wall-mount, watertight NEMA4X (IP66) enclosure with
clear, polycarbonate cover. Mounting hardware shall be
included. Combined Transmitter/Sensor systems requiring
mounting at the top of a tank shall not be accepted.
Transmitter shall include a large 4-digit LCD display
with 3/4" (19 mm) high digits that shall be visible
without opening the enclosure cover.
The transmitter shall provide for field-calibration via
built-in 2-key calibration system. Systems requiring
calibration by BCD switches or external calibrators shall
not be accepted.
Calibration data shall be permanently stored through
power interruptions without requirement of a back-up
battery.
Field calibration shall allow keypad selection of
measurement span, Range or Level operating modes, and
display units in Percent, Inches or Centimeters.
Transmitter shall permit field programmable damping to
smooth output in turbulent level conditions, and
programmable rejection time to disregard false signals
from agitators, waves and spurious echoes.
Transmitter operating temperature shall be from -13°F to
122°F (-25°C to 50°C).
Transmitter shall have an isolated 4-20mA output into a
1000 ohm maximum load. Output shall allow field
programmable offsets of 4mA and 20mA.
Provide one signal relay contact rated 1 amp. Relay shall
be programmable for single set point alarm, pump control,
and/or echo loss alarm.
Transmitter electronics shall be surge protected on AC
power input, sensor and 4-20 mA output.
Transmitter power input shall be 120VAC 50/60Hz with
power consumption of 5 watts or less.
E. ADDITIONAL FEATURES FOR INSERTION IN SPECIFICATION AS
REQUIRED:
Transmitter power input shall be 200-250VAC 50/60Hz with
maximum power consumption of 5 watts or less.
Transmitter power input shall be 24VDC with maximum power
consumption of 5 watts or less.
Have an all-Teflon sensor Model PZ32TE rated for 32'
(10 m) maximum range and operation from -40°F to 170°F (-40°C
to 76°C).
Have a PVC and Teflon sensor Model PZ52T rated for
measurement range on liquids up to 50 ft. (15.6 m).
Have a Teflon-faced flange mount sensor
model PZ34TxF rated for 32 ft (10 m) measurement range. Specify flange size
of 4”, 6” or 8”.
Include manufacturer's recommended sensor cable Junction
Box for extended cable lengths.
Sensor, connecting cable and junction boxes shall be
rated intrinsically safe to Class I,II,III, Div. I,II,
Groups C,D,E,F,G.
F. MANUFACTURER
The instrument shall be a Model LIT25 Ultrasonic Level
Transmitter as manufactured by Greyline Instruments Inc., and
warranted against defects in materials and workmanship for one
year.
Specifications are subject to change without
notice.
Please contact Greyline if you need more
information or for advice in your application. We can provide quotations and
refer you to the Greyline sales representative in your area. (To receive
complete information please provide your name, mailing address, phone and
fax numbers):